Industrial Chiller – Common Faults and Troubleshooting Guide

Industrial chillers may experience faults related to the refrigeration system, water circulation system, electrical control system, or heat dissipation system. The following table provides common problems, possible causes, inspection methods, and recommended solutions.

Fault / SymptomPossible CausesInspectionRecommended Solution
High-Pressure AlarmDirty condenser, high ambient temperature, condenser fan failure, insufficient cooling water, excessive refrigerant chargeCheck high-pressure reading, condenser fan, cooling-water flow and condenser conditionClean the condenser; check or replace the fan/pump; improve ventilation; check refrigerant charge
Low-Pressure AlarmLow refrigerant level, expansion valve blockage, evaporator icing, clogged filterCheck low-pressure reading, frosting condition and filterFind and repair leaks; recharge refrigerant according to specifications; clean or replace the filter; check the expansion valve
Compressor Does Not StartPower failure, incorrect phase sequence, overload protection, pressure protection, contactor failureCheck three-phase voltage, alarm code, contactor and protection devicesRestore power; correct phase sequence; check protection devices and contactor; reset after the fault is eliminated
Compressor OverloadAbnormal voltage, compressor mechanical problem, excessive condensing pressure, frequent startingMeasure operating current and voltageCheck power supply; reduce condensing pressure; inspect the compressor
Outlet Water Temperature Cannot Reach SetpointInsufficient cooling capacity, excessive water flow, dirty heat exchanger, high ambient temperatureCheck inlet/outlet water temperature, water flow and pressureAdjust water flow; clean the heat exchanger; inspect the refrigeration system
Outlet Water Temperature Too Low / IcingInsufficient water flow, temperature-control failure, temperature set too low, expansion valve problemCheck pump, water flow and temperature sensorIncrease water flow; check the temperature sensor; adjust the temperature setting
Water Pump Does Not RunMotor failure, phase loss, overload, blocked impellerCheck voltage, current and pump conditionCheck the motor and electrical circuit; clean the impeller; repair or replace the pump if necessary
Water Flow AlarmLow water level, blocked piping, clogged filter, water pump failureCheck tank water level, pressure, flow switch and pumpAdd water; clean the filter; check the pump and piping
Unstable Water TemperatureUnstable water flow, incorrect temperature-control parameters, fluctuating cooling loadMonitor water temperature and flow rateStabilize water flow; optimize control parameters; check the temperature sensor
Frequent Start/StopTemperature differential set too small, low cooling load, faulty temperature sensorCheck operating cycle and temperature settingsIncrease the temperature differential; check the temperature sensor; optimize control settings
Poor Heat Dissipation – Air-Cooled ChillerDirty condenser fins, fan failure, insufficient ventilation spaceCheck condenser fins, fans and airflowClean condenser fins; repair/replace the fan; ensure sufficient ventilation space
Abnormal Noise or VibrationFan/pump bearing wear, compressor problem, loose or vibrating pipesIdentify the source of noise or vibrationReplace damaged bearings/fans; inspect the compressor; secure the piping
Refrigerant LeakageLeaking brazed joints, vibration damage, defective valve sealsPerform pressure testing and leak detectionRepair the leak; evacuate the system; recharge refrigerant according to specifications
Electrical Cabinet OverheatingCooling fan failure, excessive dust, high ambient temperatureCheck cabinet temperature, cooling fan and internal dustClean the cabinet; replace the cooling fan; improve cabinet ventilation

Recommended Troubleshooting Sequence

When troubleshooting an industrial chiller, it is recommended to follow this sequence:

1. Check the alarm code

2. Check the power supply

3. Check the water circulation system

4. Check the high and low refrigerant pressures

5. Check the refrigerant charge and possible leaks

6. Check the compressor

7. Check sensors, controllers and electrical components

Important Service Note

When a high-pressure or low-pressure alarm occurs, do not simply add refrigerant.

First determine the actual cause of the abnormal pressure. Incorrect refrigerant charging may cause poor cooling performance, excessive compressor load, icing, or even compressor damage.

Quick Diagnosis

High Pressure + High Condensing Pressure

  • Dirty condenser
  • Condenser fan failure
  • Insufficient cooling-water flow
  • High ambient temperature
  • Excessive refrigerant charge

Low Pressure + Low Suction Pressure

  • Insufficient refrigerant
  • Insufficient evaporator water flow
  • Clogged filter
  • Expansion valve malfunction
  • Evaporator icing

High Compressor Current

  • Excessive condensing pressure
  • Abnormal power supply
  • Compressor mechanical failure
  • Refrigeration system abnormality